DESCRIPTION
The IQ8Control M as an efficient fire alarm control panel (FACP) for the property supervision of mid-sized to large installation.
- Max. five micromodules, with peripheral module Part No. 772477
- Max. 7 conventional esserbus circuit with extending module 772476
- Short circuit and open circuit tolerant loop operation
- Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
- Up to 127 esserbus devices (fire detectors and/or manual call points)/detector zones per loop
- Up to 32 esserbus transponders per loop/operation of wireless components (see chapter 10)
- 3 common relays, programmable and monitored
- ΤΤΥ ή RS485 ή RS232 Interface
- Operating panel with alphanumerical display (not included)
- LCD lighting screen 2x20
- Event memory for up to 10,000 events
- Printer interface for internal printer
- 2 batteries with monitoring circuit
- Monitored input for external power supply unit
Technical features:
- Supply 230VAC
- Frequency 50~60Hz
- Power 0,35Α (common operation) / 0,7Α
- Output supply 12 VDC
- Capacity of 2 battaries 12V / 24AH
- Operation temperature -5°C up to 45°C
- Protection type ΙΡ30
- Weight 11,5kg
- Dimensions 450 x 640 x 185mm